Generalized short circuit ratio (gSCR) is able to characterize the small signal stability of multi-infeed system with power electronic devices. Based on the gSCR index
the allocation optimization problem of grid-connected capacity of each feeding point is investigated when the total grid-connected capacity of photovoltaic (PV) devices (or fields) is fixed to make the small signal stability margin of multi-infeed PV system maximized.Firstly
the small signal stability analysis model for multi-infeed PV system is established.Secondly
based on the sensitivity of gSCR to grid-connected PV capacity at each feeding point
a capacity optimization method for multi-infeed PV system is proposed. Finally
with three-infeed PV system as an calculation example
the feasibility and effectiveness of the proposed capacity optimization method are verified.The simulation results show that the reasonable distribution of grid-connected PV capacity accessed to multiple points can effectively enhance the gSCR of multi-infeed PV system and increase the small signal stability margin.