In view of the under-frequency control problems of receiving-end power grid subjected to blocking faults of line-commutated converter-based high-voltage direct current(LCC-HVDC)
a feature-driven scheme of emergency load shedding is proposed by taking into account the regular response pattern after the faults occur. The changing rule of frequency and voltage at the instant of LCC-HVDC blocking fault is derived
and the low-frequency and high-voltage feature caused by time-delay inter-tripping of reactive power compensation devices is analyzed. Moreover
the partial voltage characteristics are extracted by grey correlation analysis
and the initial changing rate of frequency is used to match the action scheme by k-nearest neighbor algorithm. On the basis of the traditional under-frequency load shedding scheme
an emergency load shedding stage is added to deal with the LCC-HVDC blocking fault
and the local-monitored low-frequency and high-voltage feature is used as the operation criterion
and is adopted to match the decision table in real time to cut off the load of fault areas. Finally
a provincial power grid is taken as a case to validate the effectiveness of the proposed scheme.