a large-area blackout occurred in Brazilian power grid because of a series of chain reactions caused by a circuit breaker overload protection. As sequence
the northern and northeastern power grids were disconnected from the main power grid in Brazil
14 states in north and northeast area came to blackout
and 9 states in south
southeast and midwest area were also affected. The operation status of Brazilian power grid before the accident and the cause
process and recovery of the blackout are introduced. It is pointed out that the main causes of the accident are the lack of necessary stability analysis before the accident
the defects in security control
the misoperation of protection and the unreasonable configuration of the third line of defense. Combined with the actual situation of power grid in China
some recommendations are put forward to ensure the safe and stable operation of the power grid and to prevent blackouts. For example
attention should be paid to the setting and operation of protection and control devices.