The basic situation of high-order harmonics is introduced in Luxi station on the side of Guangxi on April 10
2017
which is based on the background of voltage source converter based high voltage direct current(VSC-HVDC)project for back-to-back asynchronous connection of Luxi station in China southern power grid. The key parts in the harmonics magnification mechanism and effects are analyzed in detail and simulated
which obtains the relationship among the high-order harmonics phenomenon
the sample part of forward control loop of VSC-HVDC grid voltage and the system harmonic impedance. Moreover
the function among the parameters of voltage feedforward control
the harmonic impedance of the system
the harmonic frequency and amplitude is derived. Then
the measures of designing reasonable filter to avoid the high-order harmonics in voltage feedforward control loop are proposed. Through the simulation and field test
the effectivity of the proposed method is verified.