陈宝平. 采用VSC-HVDC并网的直驱风电场次/超同步振荡特性[J]. 电力系统自动化, 2018,42(22):44-51.
风电、光伏经由高压直流输电系统并网外送已经成为大规模可再生能源基地的主要输送方式。对于风电引发的次/超同步振荡问题,尤其是直驱风电机组与柔性高压直流(VSC-HVDC)输电系统之间相互作用引发的次/超同步振荡问题值得深入研究。首先,分别建立直驱风电机组与VSC-HVDC的动态模型,并深入分析与推导两者之间的接口矩阵与接口动态方程,进而得到直驱风电机组经VSC-HVDC并网外送的完整动态模型。在此基础上,采用特征值分析法计算得到各振荡模式的参与因子,并根据模式参与因子判断出次/超同步振荡模式之间存在阻尼耦合。通过PSCAD/EMTDC进行时域仿真,验证了模型与特征值分析结果的正确性。进一步深入分析风电并网距离/阻抗、直驱风电机组机/网侧控制器与VSC-HVDC送/受端控制器参数对次/超同步振荡阻尼特性的影响,结果表明:同一个控制器参数可同时影响多个次/超同步模式,同一个次/超同步模式可同时受多个控制器参数影响,并且这种阻尼耦合的影响可能趋同(调节控制器参数,耦合的两种模式的阻尼比同向变化),可能趋反(调节控制器参数,耦合的两种模式的阻尼比反向变化),也可能趋同与趋反同时存在。
The delivery of wind or photovoltaic power via high voltage direct current(HVDC)system is an important approach to transmit power for large-scale renewable power bases. The sub/super-synchronous oscillation(SSO/SupSO)issues associated with wind farm is worthy of further study
especially the SSO/SupSO caused by the interaction between the direct-drive permanent magnet synchronous generator(D-PMSG)based wind turbines and the voltage source converter based HVDC(VSC-HVDC)system. Firstly
the dynamic models of D-PMSG and VSC-HVDC are established
and the interface matrix and interface dynamic equation between D-PMSG and VSC-HVDC are deeply analyzed and deduced. Then the complete dynamic model of D-PMSG interfaced with VSC-HVDC system is obtained. On this basis
the eigenvalue analysis method is applied to calculate the participation factors of the oscillation modes. At the same time
according to the participation factor of each mode
it can be concluded that there is damping coupling between the SSO mode and the SupSO mode. The time domain simulation by PSCAD/EMTDC verifies the correctness of the model and eigenvalue analysis results. Furthermore
this paper studies the influence of D-PMSG grid-connected distance/impedance
machine-side controller(MSC)/grid-side controller(GSC)of D-PMSG
sending-side controller(SEC)/receiving-side controller(REC)of VSC-HVDC system on the damping characteristics of SSO/SupSO. The results show that the same controller parameter will affect several SSO/SupSO modes
and the same SSO/SupSO mode will be affected by several controller parameters at the same time. The effect of damping coupling may exhibit convergence(the damping ratios of two coupling modes change in the same direction when adjusts controller parameters)
or anti-convergence(the damping ratios of two coupling modes change in the opposite direction when adjusts the controller parameters)
or both of convergence and anti-convergence.