the output negative sequence current of synchronverter in grid-connected operation causes serious unbalance of three-phase grid-connected current
and this situation further aggravates the instability of power grid and restricts its application in the new energy grid connection. In response to this problem
the mechanism of unbalanced current caused by the grid voltage and inverter output voltage being unsynchronized is analyzed
then a novel method to suppress the negative sequence current is proposed. Firstly
the output current of synchronverter is predicted to foresee current situation information in advance. Secondly
the value of voltage which is calculated by the differential current value from situation prediction is imported to synchronous control system to realize real time compensation. This method can realize preventive control quickly by situation orientation. The simulation results show that the proposed method can effectively restrain the negative sequence current
reduce current unbalance
and improve the dynamic performance of the control system.