has an important influence on the stability of the system. However
due to the unrational parameter setting of UEL
the positive damping effect provided by the power system stabilizer(PSS)is weakened after UEL acts. This causes the oscillation and even the serious fault of the generator frequently in the actual operation of the power grid. Based on the extended Heffron-Phillips model
a simplified model with PSS and UEL for excitation system is derived. The frequency response method is used to draw the Bode diagram of the open-loop transfer function of PSS and UEL. The frequency band of UEL and PSS is analyzed
and a specific parameter setting program of UEL is given
which can make UEL and PSS coordinated. Taking the data of Yunnan power grid for example
the single-machine infinite-bus system is developed to verify the correctness of the theory in simulation software of PSASP and MATLAB. The simulation results show that
after the UEL parameter is set by the frequency response method
the UEL action will not affect the output of the PSS
and UEL and PSS can cooperate to ensure the steady-state operation of the system.