The value set approach is a graphics-oriented method based on the characteristic polynomial of the system. It can be used to analyze the impacts of uncertain parameters on the system stability. This paper describes the implementation of the value set approach in the robust stability analysis of the large power system
including the treatment of large numbers
memory optimization
assessment and adjustment of system reduction
and application to Gamma-stability criterion. These techniques are vital for the actual application of the value set approach. Also the value set approach is compared with the widely used μ-based approach in terms of their robustness stability analysis
stability margin calculation
parameter impact analysis
conservativeness
and computation speed. Finally
the North China system is used to illustrate the implementation of the value set approach and test the two approaches
which reflects characteristics of the two approaches.