LCL inverter has high frequency resonance risk when connected into weak power system. Therefore
the virtual damping strategy is used with filter capacitor current as a state variable. In view of the characteristic of inconvenience of filter current acquisition using the medium-voltage converter in wind turbine
an optimization virtual damping strategy with grid side converter current as state variable is proposed to realize high frequency suppression. Meanwhile
band-pass filter and differential phase compensation are used to optimize the virtual damping strategy
which can meet the low-frequency gain requirement of closed-loop system and compensate for delay in the digital control system. Finally
the suppression theory of high frequency is verified by experiments and simulations with two typical phenomena
the start and load in weak grid caught in weak grid transient in full power operation.