A unified model for transformer core saturation is developed. The flux saturation resulting from the changes in voltage
including amplitude change and angle change
is the fundamental cause of inrush current. And the flux saturation is correlated with the moment of voltage leap
the angle difference and the amplitude. Voltage angle changes may also lead to inrush current while the voltage amplitude decreases
hence the reducing of voltage amplitude cannot be used to assert that there's no inrush current. Proceeding from the root causes of inrush current
a kind of iron core saturation criterion based on voltage integration is put forward. The proposed method can produce excitation inrush current because of transformer core saturation
which is caused by no-load closing
fault clearance
sympathetic inrush current
system fault or operation
and other abrupt changes in voltage. This criterion provides an effective and fast method for differential protection without inrush current atresia and will greatly accelerate the operation of differential protection of transformer when internal fault occurs.