An optimization method of power quality monitoring network considering the severity of substation voltage sags and the difference of power quality monitors are put forward. Firstly
the lightning density
pollution level
cable rate
and rated capacity are introduced to measure the severity of substation voltage sags. The objective and subjective combined weighting methods are used to assess the severity of substation voltage sags and its level is classified. Based on the newest power industry standard of China
the existing power quality monitors are classified into four different levels
i. e.
A
B
C
and D. The design of power quality monitoring network is presented in stages. In the first stage
the severity of substation is introduced and the conventional monitor reach area(MRA)matrix method is improved. A-type monitors are installed in some substations to ensure the voltage sags can be observed. In the second stage
different types of power quality monitors are configured based on the severity level of substations. In this way
mainly voltage sags are monitored while attending to other power quality problems. Finally
the results of simulation show the designed method has good validity and feasibility.