The traditional method for fault location of T-type lines is not able to identify the fault section correctly when the fault occurs near the T-type node
thus failing to locate the fault. To solve this problem
a novel branch identification criterion algorithm is proposed based on the principle of equal positive sequence voltage detected at both ends. It is concluded that the fault location function is monotonical and at the head and end the two values differ by approximately 180° at the fault branch
but the fault location function is also monotonical and at the head and end the two values are approximately equal at the healthy branch. With the phase difference in magnitude between the fault location function at the head and that at the end as the criterion for fault branch
the fault distance is solved using the analytical expression for fault distance. This branch identification criterion algorithm has remedied the drawback of traditional fault location methods. Despite the dead zone of fault location
no type identification is required
while the fault distance is obtained simply by calculating a few points with the corresponding formula. With its simple procedure and fast implementation
the proposed algorithm accuracy is in theory independent of fault type
fault resistance at fault point and operation mode
etc. The EMTP simulation results verify the validity and high precision of the algorithm.