Sub-module capacitors of the modular multilevel converter(MMC)are steadily charged and discharged during normal operation. Every sub-module is inserted and bypassed randomly to keep all the capacitor voltages balanced
which resulting in high complexity in MMC loss calculation. Based on the duty ratio concept of the inserted sub-module on a bridge arm
the analytical formulas of average and effective values of current flowing through the four switching devices are deduced in the whole power operation region. Taking the influence of capacitor voltage and gate resistor into account
the formulas of conducting loss and switching loss are deduced. Furthermore
since average junction temperature does not truly reflect the real working condition of switching devices
an approximation method for estimating the maximum operating junction temperature is proposed based on the detailed analysis of junction temperature ripple characteristics in every fundamental frequency cycle. Finally
an example analysis shows that the loss and junction temperature calculating results are in good agreement with the MMC operation characteristics