Doubly-fed induction generator (DFIG)-based wind turbines with virtual inertia control can contribute to the primary frequency regulation and relieve the lack of system inertia caused by high penetration of large-scale wind farms. However
DFIG-based wind turbines will exit frequency regulation if the rotor speed falls below a definite value since the kinetic energy stored in the rotor is limited. This procedure and the subsequent rotor speed recovery will lead to a secondary frequency drop. The characteristics of virtual inertia control and available kinetic energy released by DFIG-based wind turbines under different wind speed conditions are quantitatively analyzed. Then an active rotor speed protection strategy is proposed to make DFIG-based wind turbines gradually release the kinetic energy to avoid the secondary frequency drop. In the proposed strategy
a negative feedback control is adopted to release rotor kinetic energy
and its proportional and integrated parameters are set adaptively according to the operational states and capacity of the DFIG-based wind turbines. The validity and effectiveness of the proposed protection strategy is illustrated by case studies.This work is supported by National Natural Science Foundation of China (No. 51477093