Centering on the fault analysis and fault line selection scheme for the double HVDC transmission lines on same tower
based on the electrostatic coupling theory
according to the detailed parameters of lines and tower
considering the effects of overhead ground wire and the filter capacitors
a calculation method of the potential coefficient matrix is presented for the double HVDC transmission lines. Then the interline electrostatic unbalanced coupling effect is transformed into mode voltage variation by the phase-mode transformation. Based on the mode voltage variation
considering the different characteristics of ground-mode and line-mode quantum
by the definition of mode voltage variation ratio
this paper proposes a fault feature quantitative analysis scheme of double HVDC transmission lines on same tower to eliminate the influence of transition resistance. Based on the fault case of each mode voltage variation characteristics
a fault line selection method of the double HVDC transmission lines on same tower is proposed. Finally
the PSCAD/EMTDC is used to construct the double HVDC transmission lines on same tower to verify the correctness of the proposed method through all-round fault simulations. The results show that the proposed method is capable of accurately selecting a variety of complicated fault types unaffected by the fault transition resistance. This work is supported by National Natural Science Foundation of China(No. 51307065
No. 51577072)
and Fundamental Research Funds for the Central Universities(No. 2013ZZ028).