Operating characteristics and fault characteristics of microgrid obviously differ with traditional power grid
it brings a challenge to microgrid protection. A technology for fast and accurate fault location and isolation of microgrid based on GOOSE communication is proposed. Dividing the microgrid into regions and choosing any node as a center
the technology completes fault location by using the direction and overcurrent information from adjacent devices with the GOOSE communication
and realizes fault isolation by communicating GOOSE tripping signals. In the paper
microgrid characteristics on operation
fault
fault location and isolation
project implementation and verification
etc
are expounded. Currently
this technology has been used in many engineering projects
which verify the correctness and feasibility of it. It can deal with the microgrid multi sources
multi structures
multiple operation modes (closed loop
open loop
grid-connected and islanded mode
etc) and the topology changes
and can solve the microgrid fault location and isolation quickly and accurately.