
浏览全部资源
扫码关注微信
鉴于变压器式可控高抗中主电抗器匝间故障率较高,但动作灵敏性偏低的现状,文中在对变压器式可控高抗匝间故障分析的基础上,结合主电抗器的等效总漏感和两侧的漏感值在匝间故障、正常运行及其他运行工况下的不同变化规律,利用比率制动的思想,提出一种新型匝间保护原理。以表征等效总漏感变化的标准差为动作量,以表征两侧漏感变化平稳性的量为制动量,构成类比率制动式的保护新判据。当主电抗器发生匝间故障时,动作量增大,而制动量减小,新判据能够灵敏动作,当主电抗器在正常运行、区外故障及合闸充电等工况下时,动作量减小,而制动量增大,新判据可靠地不误动。仿真试验验证了新判据的有效性。
The rate of interturn fault on the transformer part of controllable shunt reactor of transformer type is high, whereas the sensitivity of protection is low. In order to solve this problem, first, the mechanism of interturn fault of transformer type reactors is analyzed, then different variation laws of leakage inductance on each side and the equivalent total leakage inductance of main reactor under normal and other operations is discussed. Based on the percentage restrain characteristic, a novel interturn fault protection principle is proposed, in which the standard deviation representing variation of the equivalent total leakage inductance is taken as action component, while the stability of variation of each side leakage inductance is taken as restraint component. That is the way to structure new protection criterion of percentage restraint characteristic. When interturn fault occurs, the action component increases and the restraint component decreases, so the new criterion can operate correctly. In contrast, the action component decreases and the restraint component increases under normal operation, external fault and etc, the new criterion will not mal-operate. Lots of simulation verify good effectiveness of the new criterion.
0
浏览量
2075
下载量
7
CSCD
关联资源
相关文章
相关作者
相关机构
京公网安备11010802024621