the currents in delta winding are not easily measurable. So the problem of current phase compensation has to be considered in the differential protection. However
using the present current phase compensation methods
the calculated differential current cannot really reflect the characteristics of the inrush. At the same time
the application based on the equivalent instantaneous inductance scheme is limited to identify the inrush. In this study
a constructing algorithm of circulating current in delta windings is proposed based on the voltage equations of two side windings. And the relationship between the circulating current and zerosequence voltage and current in Y side windings is also obtained. The algorithm has nothing to do with the neutral grounding
so that its application is wide. The simulation and experimental results verify that the algorithm is correct and effective to identify the inrush.