When earth faults occur at the end of long power lines in strong source networks
traditional zero sequence (negative sequence) directional element may not operate due to very low zero sequence (negative sequence) voltage which is lower than the threshold of the directional element
although zero sequence current reaches the set value of protection relay. Two kinds of solution to this problem are proposed: One is that using positive sequence voltage instead
when zero sequence (negative sequence) voltage is lower than the threshold of the directional element
the other is that using nondirectional zero sequence current protection with inverse time characteristic as a backup protection and applying new principle of current transformer circuit supervision.