WAN Wei,YUAN Hui,WANG Guanzhong,et al.Measurement Method for Converter Generalized Impedance in Sub- and Super-synchronous Band Based on Perturbation on Secondary Side[J].Automation of Electric Power Systems,2020,44(14):19-25.
WAN Wei,YUAN Hui,WANG Guanzhong,et al.Measurement Method for Converter Generalized Impedance in Sub- and Super-synchronous Band Based on Perturbation on Secondary Side[J].Automation of Electric Power Systems,2020,44(14):19-25. DOI: 10.7500/AEPS20200109008.
Measurement Method for Converter Generalized Impedance in Sub- and Super-synchronous Band Based on Perturbation on Secondary Side
The stability criterion based on generalized impedance fully considers the coupling effect between the grid and the converter in sub- and super-synchronous band
and can transform the analysis of system stability into that of single-input-single-output system. Injecting disturbances on the secondary side can not only measure the generalized impedance of the converter
but also have the advantages of lower cost and simpler operation compared with injecting disturbances on the primary side. To this end
a measurement method for generalized impedance of converter based on perburbation on the secondary side in sub- and super-synchronous band with an arbitrary power factor is proposed. Firstly
generalized impedance of the system and the primary-dual complex circuit considering the perturbation on the secondary side are derived. Secondly
the principle of measurement method for generalized impedance is explained from the point of view of circuit. Finally
based on the measurement principle
measurement method for the generalized impedance of converter perburbation on the secondary side in this frequency band is proposed. The proposed method is a generalization of existing measurement methods for generalized impedance. Simulation results verify the effectiveness of the proposed method.
KANG Chongqing , YAO Liangzhong . Key scientific issues and theoretical research framework for power systems with high proportion of renewable energy [J]. Automation of Electric Power Systems , 2017 , 41 ( 9 ): 1 - 11 .
LU Zongxiang , HUANG Han , SHAN Baoguo , et al . Morphological evolution model and power forecasting prospect of future electric power systems with high proportion of renewable energy [J]. Automation of Electric Power Systems , 2017 , 41 ( 9 ): 12 - 18 .
YUAN Xiaoming , CHENG Shijie , HU Jiabing . Multi-time scale voltage and power angle dynamics in power electronics dominated large power systems [J]. Proceedings of the CSEE , 2016 , 36 ( 19 ): 5145 - 5154 .
XIE Xiaorong , LIU Huakun , HE Jingbo , et al . Small-signal impedance/admittance network modeling for grid-connected renewable energy generation systems [J]. Automation of Electric Power Systems , 2017 , 41 ( 12 ): 26 - 32 .
YUAN Hui , XIN Huanhai , WANG Kang , et al . Instability mechanism analysis of inverters connected to weak grid during severe voltage sag on remote grid side [J]. Automation of Electric Power Systems , 2018 , 42 ( 22 ): 38 - 43 .
XU Luyao , LAN Zhou , CHEN Fei , et al . Analysis on impact of reactive power control on stability of grid-connected converter in weak grid [J]. Automation of Electric Power Systems , 2019 , 43 ( 15 ): 56 - 63 .
XIE Xiaorong , WANG Yin , LIU Huakun , et al . Detection method for sub-synchronous and super-synchronous harmonic phasors in power system [J]. Automation of Electric Power Systems , 2016 , 40 ( 21 ): 189 - 194 .
BIAN Xiaoyan , DING Yang , MAI Kun , et al . Subsynchronous oscillation caused by grid-connection of offshore wind farm through VSC-HVDC and its mitigation [J]. Automation of Electric Power Systems , 2018 , 42 ( 17 ): 25 - 33 .
JOHN A , CATHEY C , SHUN-HSIEN H . ERCOT experience with sub-synchronous control interaction and proposed remediation [C]// PES T&D 2012, May 7-10 , 2012 , Orlando , USA: 1-5 .
ZHU Xinyao , SUN Haishun , CHEN Meng , et al . A novel approach to construct the state-space model of power system grid and its application in SSR study [J]. Proceedings of the CSEE , 2014 , 34 ( 4 ): 605 - 612 .
SUN Jian . Impedance-based stability criterion for grid-connected inverters [J]. IEEE Transactions on Power Electronics , 2011 , 26 ( 11 ): 3075 - 3078 .
LIU Wei , XIE Xiaorong , HUANG Jinkui , et al . Frequency-coupled impedance model and stability analysis of grid-connected converter [J]. Automation of Electric Power Systems , 2019 , 43 ( 3 ): 138 - 146 .
NIAN Heng , YANG Hongyu . Impedance modeling and stability analysis of grid-connected inverters under unbalanced operation conditions [J]. Automation of Electric Power Systems , 2016 , 40 ( 10 ): 76 - 83 .
XIN Huanhai , LI Ziheng , DONG Wei , et al . Generalized-impedance and stability criterion for grid-connected converters [J]. Proceedings of the CSEE , 2017 , 37 ( 5 ): 1277 - 1293 .
XU Luyao , XIN Huanhai , HUANG Linbin , et al . Symmetric admittance modeling for stability analysis of grid-connected converters [J]. IEEE Transactions on Energy Conversion , 2019 , 35 ( 1 ): 434 - 444 .
MENG Zhiquan , XIN Huanhai , DONG Wei , et al . Generalized-impedance measurement for grid-connected converters based on perturbation in control system [J]. Proceedings of the CSEE , 2018 , 38 ( 18 ): 5381 - 5391 .
DONG Wei , XIN Huanhai , LI Ziheng , et al . Primal-dual complex circuit of grid-connected converters for oscillation analysis [J]. Proceedings of the CSEE , 2017 , 37 ( 22 ): 6500 - 6515 .
CAO Wenchao , MA Yiwei , XUAN Zhang , et al . Sequence impedance measurement of three-phase inverters using a parallel structure [C]// IEEE Applied Power Electronics Conference and Exposition (APEC) , March 15 - 19 , 2015 , Charlotte, USA: 3031 - 3038 .
SHAH S , PARSA L . Impedance modeling of three-phase voltage source converters in dq sequence, and phasor domains [J]. IEEE Transactions on Energy Conversion , 2017 , 32 ( 3 ): 1139 - 1150 .
Wide-band Impedance Measurement Device for Medium-voltage DC Systems and Its Control Based on Pseudo-random Binary Sequence
Current-based Control Strategy for Grid-connected Converter with Energy Storage and Embedded Synchronous Generator Support Characteristics
Review on Grid-following/Grid-forming Hybrid Mode Control for Grid-connected Converter in High Penetration Rate of Renewable Energy Generation
Multi-mode Flexible Switching Strategy of Multi-functional Grid-connected Converters for Active Support to Transient Voltage
High-efficiency Eigenvalue Calculation Method for Large-scale Time-delay Power System Based on Partial Infinitesimal Generator Discretization with Implicit Runge-Kutta
Related Author
XU Guangqiang
ZHU Shuchao
WANG Jianhua
ZHAO Jianfeng
XIAO Xiaolong
JI Zhendong
LI Yong
CAO Yijia
Related Institution
School of Electrical Engineering, Southeast University
School of Automation, Nanjing University of Science and Technology
Electric Power Research Institute of China Southern Power Grid Company Limited
School of Electrical and Information Engineering, Hunan University
National and Local Joint Engineering Laboratory for Renewable Energy Access to Grid Technology (Hefei University of Technology)