WANG Zhihua,SHI Bonian,LIU Hao,et al.All-application-field Compensation Method for Improving Measurement Accuracy of Synchrophasor Measurement Unit for Distribution Network[J].Automation of Electric Power Systems,2020,44(18):39-45.
WANG Zhihua,SHI Bonian,LIU Hao,et al.All-application-field Compensation Method for Improving Measurement Accuracy of Synchrophasor Measurement Unit for Distribution Network[J].Automation of Electric Power Systems,2020,44(18):39-45. DOI: 10.7500/AEPS20191116004.
All-application-field Compensation Method for Improving Measurement Accuracy of Synchrophasor Measurement Unit for Distribution Network
The distribution network is seriously affected by noise and harmonics and its line length is usually short
so it is necessary to develop synchrophasor measurement unit for distribution network (D-PMU) to realize the monitoring
control and state estimation of distribution network. High-precision measurement is the cornerstone for the observability and controllability of the distribution network
and the alternating current (AC) sampling module is the kernel of the measurement of D-PMU. Based on the analysis of the source of hardware error in AC sampling module
an all-application-field compensation method in the engineering with gradual error reduction is proposed to improve the measurement accuracy: ① through factory calibration
the fixed system error is eliminated; ② through full-range compensation based on the cubic polynomial fitting
the tested device can meet the accuracy required in application; ③ through temperature drift compensation based on the quadratic polynomial fitting
the field operation accuracy of D-PMU is improved. Using the proposed all-application-field compensation method
a D-PMU is modified for verification
and the artificial simulation environment is built. Test results show that the all-application-field compensation method can effectively improve the phasor measurement accuracy of D-PMU.
XIE Xiaolei , LIU Yadong , SUN Peng , et al . Development of novel PMU device for distribution network lines [J]. Automation of Electric Power Systems , 2016 , 40 ( 12 ): 15 - 20 .
WANG Jinli , WEI Chunyuan , PAN Xu , et al . Fast matching method for key nodes of smart distribution network oriented to operational optimization requirements [J]. Power System Technology , 2019 , 43 ( 3 ): 848 - 855 .
WANG Bin , SUN Huadong , ZHANG Daonong . Review on data sharing and synchronized phasor measurement technique with application in distributions system [J]. Proceedings of the CSEE , 2015 , 35 ( Supplement 1 ): 1 - 7 .
LIN Zhenzhi , LIU Yong , JIA Yong , et al . Dynamic performance test of single-phase phasor measurement units [C]// 2011 IEEE Power and Energy Society General Meeting , July 24 - 28 , 2011 , Detroit, USA: 1 - 7 .
WACHE M , MURRAY D C . Application of synchrophasor measurements for distribution networks [C]// 2011 IEEE Power and Energy Society General Meeting , July 24 - 28 , 2011 , Detroit, USA: 1 - 4 .
DING Feng , BOOTH C D . Applications of PMUs in power distribution networks with distributed generation [C]// Proceedings of 2011 46th International Universities Power Engineering Conference (UPEC) , September 5 - 8 , 2011 , Soest, Germany: 1 - 5 .
ZHANG Hengxu , JIN Zongshuai , LIU Yutian , et al . Wide-area measurement system light and its application in China [J]. Automation of Electric Power Systems , 2014 , 38 ( 22 ): 85 - 90 .
LI Jue , LIU Hao , TIAN Jiannan , et al . Communication protocol and performance analysis for the PMU of distribution network [J]. Journal of Electric Power Science and Technology , 2019 , 34 ( 2 ): 3 - 10 .
CASTELL P , LIXIA M , MUSCAS C . Impact of the model on the accuracy of synchrophasor measurement [J]. IEEE Transactions on Instrumentation and Measurement , 2012 , 62 ( 8 ): 2178 - 2188 .
BI Tianshu , LIU Hao , YANG Qixun , et al . Dynamic performance of PMU algorithm and its testing system [J]. Automation of Electric Power Systems , 2014 , 38 ( 1 ): 62 - 67 .
LIU Hao , BI Tianshu , YANG Qixun . The evaluation of phasor measurement units and their dynamic behavior analysis [J]. IEEE Transactions on Instrumentation and Measurement , 2013 , 62 ( 6 ): 1479 - 1485 .
LIU Hao , BI Tianshu , YANG Qixun . The impact of digital filter on the PMU dynamic performance [J]. Proceedings of the CSEE , 2012 , 32 ( 19 ): 49 - 57 .