An Improved Adaptive Reclosing Strategy of Four-terminal Flexible DC Grid with Hybrid Modular Multilevel Converter
The flexible DC grid is an important technical measure for large-scale long-distance overhead line transmission of renewable energy. However
overhead lines are more prone to instantaneous short-circuit faults than DC cables
and they need to be reclosed quickly after the fault is cleaned. If a permanent fault occurs in the DC grid
the conventional fault identification method based on the active signal injection of the converter is likely to cause great interference to the stable operation of the DC grid. To solve these problems
an improved adaptive reclosing strategy with active signal injection of the hybrid modular multilevel converter (MMC) for flexible DC grids is presented. Active signal control is added to the hybrid MMC pole controller
so that the flexible DC grid can realize the identification of the fault properties without interrupting the power transmission. This method has strong resistance to transition resistance and does not affect the power transmission stability of the flexible DC grid. The electromagnetic transient model of the four-terminal flexible DC grid with hybrid MMC is built in PSCAD/EMTDC. The simulations verify the effectiveness of the method in the flexible DC grid equipped with hybrid MMC and mechanical DC circuit breakers.
SUN Kaiqi , LI Kejun , LIU Zhijie , et al . Coordinated operation strategy for pumped storage and renewable energy generation based on VSC-DC integration [J]. Automation of Electric Power Systems , 2019 , 43 ( 8 ): 41 - 48 .
CAO Shuai , XIANG Wang , YAO Liangzhong , et al . AC and DC fault ride-through strategies for wind power integration via hybrid MMC-HVDC [J]. Automation of Electric Power Systems , 2018 , 42 ( 7 ): 37 - 43 .
LU Xiaojun , XIANG Wang , LIN Weixing , et al . Analysis on analytical modeling and power operating zone of hybrid modular multilevel converter [J]. Automation of Electric Power Systems , 2018 , 42 ( 7 ): 76 - 84 .
LI Mengbo , XIANG Wang , ZUO Wenping , et al . DC-DC autotransformer with uninterrupted operating capability during DC fault [J]. Automation of Electric Power Systems , 2018 , 42 ( 4 ): 82 - 88 .
LI Yan , HUANG Yu , GONG Yanfeng , et al . Analysis on overvoltage mechanism of DC line fault in flexible DC grid [J]. Automation of Electric Power Systems , 2020 , 44 ( 5 ): 146 - 153 .
GUO Xianshan , ZHOU Yang , MEI Nian , et al . Construction and characteristic analysis of Zhangbei flexible DC grid [J]. Power System Technology , 2018 , 42 ( 11 ): 3698 - 3707 .
SONG Guobing , GAO Shuping , CAI Xinlei , et al . Survey of relay protection technology for HVDC transmission line [J]. Automation of Electric Power Systems , 2012 , 36 ( 22 ): 123 - 129 .
徐政 . 柔性直流输电系统 [M]. 北京 : 机械工业出版社 , 2017 .
XU Zheng . Voltage source converter based HVDC power transmission systems [M]. Beijing : China Machine Press , 2017 .
SONG Guobing , WANG Ting , ZHANG Chenhao , et al . Adaptive auto-reclosing of DC line based on characteristic signal injection with FB-MMC [J]. Power System Technology , 2019 , 43 ( 1 ): 149 - 156 .
CAI Pucheng , XIANG Wang , ZHOU Meng , et al . Research on adaptive reclosing of DC fault based on active signal injected by hybrid MMC [J]. Proceedings of the CSEE , 2020 , 40 ( 12 ): 3867 - 3878 .
WANG Shuai , BI Tianshu , JIA Ke . Single terminal fault location for MMC-HVDC transmission line using active pulse [J]. Transactions of China Electrotechnical Society , 2017 , 32 ( 1 ): 12 - 19 .
WANG T , SONG G , KAZMI S T , et al . Adaptive single-pole auto-reclosing scheme for hybrid MMC-HVDC systems [J]. IEEE Transactions on Power Delivery , 2019 , 34 ( 6 ): 2194 - 2203 .
LI Bin , HE Jiawei , LI Ye , et al . Novel restart scheme of DC fault for flexible DC transmission system [J]. Automation of Electric Power Systems , 2017 , 41 ( 12 ): 77 - 85 .
ZHANG Junjie , XIANG Wang , LIN Weixing , et al . DC fault protection of VSC-HVDC grid based on hybrid MMC and DC switch [J]. Electric Power Construction , 2017 , 38 ( 8 ): 52 - 58 .
XIANG W , YANG S , XU L , et al . A transient voltage based DC fault line protection scheme for MMC based DC grid embedding DC breakers [J]. IEEE Transactions on Power Delivery , 2019 , 34 ( 1 ): 334 - 345 .
ZHANG S , ZOU G , LI B , et al . Fault property identification method and application for MTDC grids with hybrid DC circuit breaker [J]. International Journal of Electrical Power and Energy Systems , 2019 , 110 : 136 - 143 .
ZHOU Meng , XIANG Wang , LIN Weixing , et al . Active current-limiting control to handle overhead line fault in DC grid [J]. Power System Technology , 2018 , 42 ( 7 ): 2062 - 2072 .
PAN Yuan , YUAN Zhao , CHEN Lixue , et al . Research on the coupling mechanical high voltage DC circuit breaker [J]. Proceedings of the CSEE , 2018 , 38 ( 24 ): 7113 - 7120 .
VRANA T K , DENNETIÈRE S , JARDINI J , et al . The CIGRE B4 DC grid test system version 2013 [EB/OL]. [ 2020-05-01 ]. https://wenku.baidu.com/view/0725c71cddccda38376baf86.html https://wenku.baidu.com/view/0725c71cddccda38376baf86.html .