CHEN Le,SHE Zhenqiu,WANG Junsheng,et al.Analysis and Countermeasures of Operation Conditions of Metallic-bypass Branch in UHVDC Transmission System[J].Automation of Electric Power Systems,2020,44(02):227-233.
CHEN Le,SHE Zhenqiu,WANG Junsheng,et al.Analysis and Countermeasures of Operation Conditions of Metallic-bypass Branch in UHVDC Transmission System[J].Automation of Electric Power Systems,2020,44(02):227-233. DOI: 10.7500/AEPS20190618010.
Analysis and Countermeasures of Operation Conditions of Metallic-bypass Branch in UHVDC Transmission System
In the ultra-high voltage direct current (UHVDC) projects which is based on the structure of dual 12-pulses valve groups in series
the following actions may lead to the metallic-bypass branch operation: the manual and auto sequence control of switching equipment in DC yard
the protective blocking of one pole
the online protective quitting of valve groups. This paper describes the forming process of the metallic-bypass branch operation and proposes the corresponding countermeasures. The prevention should be taken as the major principle in dealing with metallic bypass branch operation
and the isolation methods should be taken as the supplementary measures,such as the pole isolation and the failure protection of neutral bus switch. The countermeasures described in this paper have been applied in the ±800 kV UHVDC project from northwest Yunnan to Guangdong in China Southern Grid. The on-site test and simulation test show the problem of metallic-bypass branch operation in dual 12-pulses valve groups in series has been effectively solved.
ZENG Qingke , LI Fengfeng , HAO Yuedong , et al . Analysis on spill current of UHVDC transmission system in monopole-grounded return operation mode and its countermeasures [J]. Automation of Electric Power Systems , 2014 , 38 ( 22 ): 123 - 127 .
PENG Chang , WEN Jialiang , WANG Xiuhuan , et al . Development of DC transfer switch in ultra high voltage DC transmission systems [J]. Proceedings of the CSEE , 2012 , 32 ( 16 ): 151 - 156 .
LI Xingwen , GUO Ze , FU Mingli , et al . Current commutation characteristics and its influential factors for high-voltage direct current transfer switches [J]. High Voltage Engineering , 2018 , 44 ( 9 ): 2856 - 2864 .
HU Yuyang , YU Shanshan . Instance analysis of conversion between ground return and metallic return in Gezhouba-Nanqiao HVDC transmission system [J]. Automation of Electric Power Systems , 2017 , 41 ( 23 ): 150 - 155 .
YANG Wankai , YI Fuquan , ZENG Nanchao , et al . Analysis of UHVDC neutral bus switch reclosing protection maloperation [J]. Power System Technology , 2016 , 40 ( 6 ): 1759 - 1765 .
LI Xinnian , LI Tao , LÜ Pengfei , et al . Analysis on the strategy of converter entry/exit for Xiangjiaba to Shanghai UHVDC project [J]. High Voltage Engineering , 2011 , 37 ( 5 ): 1232 - 1238 .
HUO Pengfei , WANG Guogong , LIU Min , et al . The DC protection block strategy in Xiangjiaba-Shanghai ±800 kV UHVDC transmission project [J]. Power System Protection and Control , 2011 , 39 ( 9 ): 137 - 144 .
ZHANG Ailing , LIU Tao , LI Shaohua . Research on control strategy for ESOF & bypass switch operation in Yunnan-Guangdong UHVDC project [J]. Power System Protection and Control , 2011 , 39 ( 13 ): 121 - 125 .
ZHANG Qingwu , WANG Yongping , CHEN Xiaojun , et al . Design and development of control and protection system for UHVDC [J]. Automation of Electric Power Systems , 2013 , 37 ( 21 ): 88 - 93 .
WANG Junsheng , LIU Huanzhang . Pre-acceleration of protection for HVDC transmission lines [J]. Automation of Electric Power Systems , 2019 , 43 ( 9 ): 1 - 8 . DOI: 10.7500/AEPS20190102001 http://dx.doi.org/10.7500/AEPS20190102001 .
CHEN Xiaojun , HE Luya , SUN Yang , et al . Comparative analysis on control and protection system of ±800 kV UHVDC and ±500 kV HVDC [J]. East China Electric Power , 2012 , 40 ( 3 ): 462 - 466 .
CHEN Xilei , TIAN Jie , HUANG Zhiling , et al . Impact of bypass pair strategy on neutral-bus arrester under emergency shutdown of HVDC [J]. East China Electric Power , 2010 , 38 ( 9 ): 1355 - 1358 .
WANG Junsheng , ZHU Bin . Analysis of fault clearing actions under single phase to ground fault of lines connecting transformer and inverter valve [J]. Automation of Electric Power Systems , 2010 , 34 ( 23 ): 119 - 123 .
WU Linping , WANG Junsheng , YU Jiang . The optimization of HVDC pole-isolating methods and analysis on the related problems [J]. Southern Power System Technology , 2011 , 5 ( 3 ): 31 - 35 .