ZHU Yan,LU Yuping,HUANG Tao.Sufficient Current Amplitude Differential Protection Considering Frequency Characteristic of Harmonics for Distribution Network with Wind Power[J].Automation of Electric Power Systems,2020,44(16):130-136.
ZHU Yan,LU Yuping,HUANG Tao.Sufficient Current Amplitude Differential Protection Considering Frequency Characteristic of Harmonics for Distribution Network with Wind Power[J].Automation of Electric Power Systems,2020,44(16):130-136. DOI: 10.7500/AEPS20190530010.
Sufficient Current Amplitude Differential Protection Considering Frequency Characteristic of Harmonics for Distribution Network with Wind Power
Wind power integrated into distribution network poses challenges to traditional protection schemes in distribution network. Considering the change of distribution network structure and the relative backwardness of the communication conditions
this paper extracts the general characteristics of the most fault current amplitudes
and puts forward the principle of sufficient current amplitude differential protection. Taking the doubly-fed induction wind generator as the representative form of wind power integrated into distribution network
the harmonic frequency characteristics of short-circuit current with the control strategy of low voltage ride through are analyzed. The concept of spectrum index is proposed to measure the proportion of harmonic components
so as to measure the frequency characteristic difference of current harmonic between the wind power side and the power system side. Based on this,a new criterion of sufficient current amplitude differential protection considering the harmonic frequency characteristics is proposed as the supplementary of the sufficient protection scheme. The improved protection scheme makes full use of the fault current amplitude and harmonic frequency information
and improves the sensitivity and reliability of the protection. Finally
the rationality of the protection scheme is verified by MATLAB/Simulink simulation.
ZHAO Shanglin , WU Zaijun , HU Minqiang , et al . Thought about protection of distributed generation and microgrid [J]. Automation of Electric Power Systems , 2010 , 34 ( 1 ): 73 - 77 .
PENG Ke , ZHANG Cong , XU Bingyin , et al . Key issues of fault analysis on distribution system with high-density distributed generations [J]. Automation of Electric Power Systems , 2017 , 41 ( 24 ): 184 - 192 .
LI Naiyong , LIANG Jun , ZHAO Yishu , et al . Protection schemes for distribution network considering the randomness of distributed generations [J]. Automation of Electric Power Systems , 2011 , 35 ( 19 ): 33 - 38 .
DENG Sanxing , ZHANG Xuemin , LIU Hui , et al . Quantitative evaluation of low voltage ride-through control strategies for doubly-fed induction generators [J]. Automation of Electric Power Systems , 2018 , 42 ( 21 ): 28 - 38 .
PANNELL G , ATKINSON D J , ZAHAWI B . Minimum-threshold crowbar for a fault-ride-through grid-code-compliant DFIG wind turbine [J]. IEEE Transactions on Energy Conversion , 2010 , 25 ( 3 ): 750 - 759 .
ZHANG Baohui , GUO Danyang , WANG Jin , et al . Impact of wind farm integration on relay protection (5): impact of wind farms dispersedly connected to distribution network on current protection [J]. Electric Power Automation Equipment , 2013 , 33 ( 5 ): 1 - 6 .
Power System Relaying Committee . Impact of distributed resources on distribution relay protection [EB/OL]. [ 2019-05-01 ]. http://www.pes-psrc.org http://www.pes-psrc.org .
Standard Coordinate Committee 21.IEEE standard for interconnecting distributed resources with electric power systems: IEEE Std. 1547—2003 [S]. 2003 .
OKEDU K E , MUYEEN S M , TAKAHASHI R , et al . Wind farms fault ride through using DFIG with new protection scheme [J]. IEEE Transactions on Sustainable Energy , 2012 , 3 ( 2 ): 242 - 254 .
MA Jing , WANG Xi , MI Chao , et al . A new adaptive protection approach for distribution network containing distributed generation [J]. Power System Technology , 2011 , 35 ( 10 ): 204 - 208 .
CHEN Xiaolong , LI Yongli , TAN Huizheng , et al . An adaptive instantaneous trip protection based on positive-sequence current for distribution network with IBDG [J]. Automation of Electric Power Systems , 2015 , 39 ( 9 ): 107 - 112 .
JIA Wei , ZHANG Yongsheng , WU Shoushan . Research on directional element without voltage in distribution network protection with DG [J]. Power System Protection and Control , 2011 , 39 ( 2 ): 94 - 97 .
HUNT R , ADAMIAK M , KING A , et al . Pilot protection for distribution lines using digital radio [J]. IEEE Industry Applications Magazine , 2009 , 15 ( 5 ): 51 - 60 .
XU Sixuan , LU Yuping . Current amplitude differential protection for distribution system with DG [J]. Transactions of China Electrotechnical Society , 2015 , 30 ( 18 ): 164 - 170 .
LIN Xia , LU Yuping , WANG Lianhe . New current protection scheme considering distributed generation impact [J]. Automation of Electric Power Systems , 2008 , 32 ( 20 ): 50 - 56 .
WANG Ting , SONG Guobing , ZHANG Chenhao , et al . Active detection based three-phase auto-reclosing method for 110 kV single outgoing line in wind farm [J]. Automation of Electric Power Systems , 2019 , 43 ( 19 ): 149 - 159 .