there are some problems for online identification and alarm method of subsynchronous oscillation (SSO) based on phasor measurement unit (PMU). Parameter identification method only identifies the frequency and amplitude
and does not identify attenuation factor. Alarm threshold values need to be determined by personal experiences. Therefore
it is difficult to guarantee the rapidity and reliability of alarm criterion. In view of the problems mentioned above
the on-line monitoring SSO method is proposed combing synchroextracting transform (SET) and naive Bayes (NB)
which is one of the machine learning method. SET can quickly and accurately identify the mode parameters of SSO
and NB can automatically realize online warning. Firstly
SET identifies the historical data of SSO
and then NB method learns from the identified frequency and attenuation factor
which helps to generate a NB classifier. Secondly
when there are new upload oscillation data of PMU
the oscillation frequency and attenuation factor are identified by SET at the first step. Then
NB classifier is used to deal with these parameters to determine whether SSO occurs or not and realize accurate on-line early warning
so as to realize the on-line monitoring of SSO. The simulation of the second IEEE benchmark model verifies the effectiveness of the proposed method.