To explain the mechanism of sub-synchronous resonance(SSR)in doubly-fed induction generator(DFIG)based wind turbine system under series compensation
a static reference frame impedance model of DFIG based wind turbine is established. Firstly
the dq impedance model of DFIG based wind turbine is transformed into complex vector form and its frequency-domain impedance model is derived by frequency transformation. Based on the physical interpretation represented by the impedance model
the influence of controller and network parameters on equivalent impedance and SSR frequency of grid-connected system is analyzed using equivalent RLC series circuit. Damping control and virtual inductance control are proposed to mitigate SSR
which can increase the damping of SSR region and reduce the SSR frequency of the system
respectively. Finally
the accuracy of the model and theoretical analysis is verified by simulation.
Stability Control Strategy for Grid-connected Converter Based on Decoupling of Phase-locked Loop and Current Loop
Impedance Modeling of Direct-drive Permanent Magnet Synchronous Generator in Complex Field and Its Feature Analysis Considering Frequency Coupling Characteristics
Simplified Modeling Method of Sequence Impedance and Grid-connected Stability Analysis for Three-phase LCL Inverter
Small-signal Stability Assessment Method for DC Distribution System with Multiple Voltage Levels
Related Author
LI Zhen
HE Yang
TANG Kaixuan
LI Xiaomeng
QU Bei
TANG Xin
ZOU Zhixiang
YAO Yiyang
Related Institution
State Key Laboratory of Disaster Prevention & Reduction for Power Grid, Changsha University of Science and Technology
School of Electrical Engineering, Southeast University
School of Electrical and Electronic Engineering, North China Electric Power University
Center for Advanced Power Conversion Technology and Equipment, Southeast University
State Grid Jiangsu Electric Power Co., Ltd. Research Institute