An improved cutting plane consensus algorithm is adopted to optimize the optimal power flow problem in the active distribution network with high penetration of photovoltaic. Firstly
the power flow equation is approximated linearly
the node voltage is expressed linearly by node injection power
and hence a quadratic programming model including network loss and penalty cost of the curtailment of photovoltaics is constructed. Then
using Lagrange dual relaxation technology to decouple the centralized model
the distribution network and the photovoltaic inverters are taken as independent agents. For each agent
a master problem is built to approximate the original problem and only the cutting plane constraints are transferred between agents. On the premise of satisfying the coupling constraint between any two agents
the optimal solutions can be obtained for each agent. The agents are independent of each other and with good confidentiality. They do not need an upper level coordinator
and can converge to the optimal solution when the cutting plane information is occasionally lost. Finally
an actual rooftop photovoltaic system and a 33-bus system are tested to demonstrate the correctness and effectiveness of the proposed method.
Optimal Power Flow of Integrated Hydrogen-Electricity Energy System Based on Reduced-dimension Projection
Review on Optimization Methods for New Power System Dispatch Based on Deep Reinforcement Learning
Review and Prospect of Inter-Regional and Inter-Provincial Power Trading in China
Assessment on Distributed Generation Accomodation Capability for Distribution Network Based on Uncertain Optimal Power Flow
Related Author
PENG Hongyi
YAN Mingyu
ZHOU Yijia
PENG Hongyi
YAN Mingyu
ZHOU Yijia
FENG Bin
HU Yijie
Related Institution
State Key Laboratory of Advanced Electromagnetic Engineering and Technology (Huazhong University of Science and Technology)
State Key Laboratory of Advanced Electromagnetic Engineering and Technology (School of Electrical and Electronic Engineering, Huazhong University of Science and Technology)
College of Electrical Engineering, Zhejiang University
Zhijiang Laboratory
Department of Electrical Engineering, Tsinghua University