During the initial operation of Xinsong-Dongfang ultra-high voltage direct current(UHVDC)project
the delayed operation of sending generators results in insufficient capacity of island short-circuit and risks such as overvoltage and low-order resonance. In order to ensure the safety of devices when the UHVDC project passively jumps into island operation
this paper proposes a blocking strategy for Xinsong-Dongfang UHVDC project jumped into island operation
i. e.
add the automatic blocking function for island operation in the DC station control system
and adopt a low-power anti-false criterion of AC tie-line to effectively prevent the strategy from malfunctioning in the grid-connected mode. A strategy as follows can effectively reduce the overvoltage of the island UHVDC blocking and ensure the safety of related equipment: firstly
cut off all the filters; secondly
delay the UHVDC blocking; thirdly
the stability control system cut all generators in island operation mode. Field application shows that all AC filters can be cut within 300 ms after the UHVDC project jumps into island operation
and the UHVDC blocking is initiated after a delay time of 30 ms
then the stability control system delays after bipolar blocking
while all the island generators are accurately cut. The blocking logic and the stability control strategy are correct
and the overvoltage and frequency meet the requirement of the specification.