The fast grounding switch has both voltage and current double arc suppression effect
but traditional analysis does not take the effect of voltage drop on the current at fault point into account
which needs further analysis of arc suppression performance. Considering the dynamic parameters of the fault line
a single-phase grounding fault model of distribution network with fast grounding switch is established
and the expression of the fault point current is derived by the symmetrical component method. The calculation results show that the fault current is affected by multiple factors such as load current of fault line
sequence impedance
interphase capacitance
fault distance and transition resistance. The model of fast grounding switch arc circuit is analyzed to show that the fast grounding switch can effectively suppress intermittent arc grounding overvoltage. But in the process of stable low flame retardancy caused by the dynamic parameters of the fault line
the fast grounding switch may increase the fault point current
which is not conducive to the extinguishing of the arc. Combined with the advantages and disadvantages of the fast grounding switch
suggestions are put forward for its arc suppression application of fast grounding switch or cooperating with Petersen coil. Finally
the results of the analysis are verified by MATLAB simulation.