To make full use of smart grounding system to solve single-phase grounding fault in the neutral non-effectively grounding distribution systems
based on the simple description of basic principles
the transient process during the closing and opening period of the grounding switch and inhibition measures are analyzed in detail
the techniques of transient process reduction and grounded phase identification error correction are described with the corresponding analysis
the design parameters of intermediate resistance of grounding are obtained. The method of identification and location of the single-phase grounding position in permanent single-phase grounding fault for systems with neutral ungrounded and with neutral grounded through an arc-suppression coil are investigated
respectively
together with their design considerations. A method of identifying the disconnected feeder is put forward based on the ratio of zero sequence current before and after accessing the pulse grounding transformer. The simulation and experimental results are in consistent with the theoretical analysis
which shows the feasibility and effectiveness of the proposed method.
Coupling Characteristic and Control Strategy for Loop Closing Device Based on Improved Phase Shifting Transformer Under Three-phase Asymmetry Condition
Automatic Processing of Single-phase Grounding Fault in Distribution Network Based on Fault Phase Grounding
中压配电网单相接地故障熄弧后的电气特征分析
Related Author
CAI Fudong
JI Xingquan
JIANG Haiyang
ZHANG Yumin
YANG Ming
WANG Chengfu
WANG Pengwei
XU Bingyin
Related Institution
Shandong Senter Electronic Co., Ltd.
Key Laboratory of Power System Intelligent Dispatch and Control of Ministry of Education (Shandong University)
College of Electrical Engineering and Automation, Shandong University of Science and Technology
School of Electrical and Electronic Engineering, Shandong University of Technology
Shandong Kehui Electric Power Automation Co., Ltd.