a power oscillation occurred in Silin Hydropower Plant during the period of No. 2 generator increasing its output power and the plant voltage dropped continuously. Based on the on-site record curve and simulation by BPA software and RTDS
the causes of power oscillation are analyzed in detail
and the scene of the power oscillation is reproduced. In response to the problems including that the generator's reactive power mode is set incorrectly and the power system stabilizer(PSS)has some defect in low frequency band because of measurement errors in rotator speed
the application principle of the plant reactive power control mode is proposed and the damping character is promoted by optimizing PSS's ramp function setting. The scheme has been put into operation in Silin Hydropower Plant after RTDS and on-site test
and it shows that the damping characteristic of the plant is improved effectively. The suggestions for improvement of PSS's setting criterion are proposed combined with the on-site test.
Preliminary Study on Stabilizer for New Power Systems
Mechanism Analysis of Power Low-frequency Oscillations in Parallel System of Multiple Virtual Synchronous Generators
Analysis on Characteristics of DC Dynamical Power and Frequency Response for AC-DC-AC Asynchronous-interconnection System Under Quasi-synchronous Control
Related Author
XIE Xiaorong
LI Haozhi
ZHANG Dan
WANG Xi
LIU Yuxin
PENG Ke
ZHAO Zida
JIANG Yan
Related Institution
State Key Laboratory of Power System Operation and Control(Tsinghua University)
Department of Electrical Engineering, Tsinghua University
School of Electrical and Electronic Engineering, Shandong University of Technology
Electric Power Research Institute of China Southern Power Grid Company Limited
Power Dispatching and Control Center of China Southern Power Grid