With the development of distributed generation and power electronic technology
DC distribution network based on voltage source converter(VSC)has many advantages
such as flexible access
high reliability and good economic efficiency. Based on the detailed analysis of the VSC steady-state power flow model
the power flow calculation of multi-terminal DC distribution network is studied through taking into account the operation control strategy of the DC distribution network. In the process of power flow calculation
it uses the node correlation matrix to search automatically the network structure and open automatically the looped network. It proposes a unified power correction method for looped network and droop node
and takes into account the power limitation and control mode conversion of VSC. With the modified IEEE 14-node DC distribution example system
it verifies the correctness and validity of the proposed power flow calculation method.