Low voltage direct current(LVDC)distribution network can reduce the power capacity of each bus section by sectionalizing buses
so it is possible to provide DC power in a wide range. Due to the diversity of distribution network load and the randomness of electricity consumption
the voltage of DC buses fluctuate frequently
and the energy storage devices should be arranged in a sensitive load area to improve the quality and the reliability of power supply. For this purpose
a topology of a triple-phase DC/DC converter is firstly chosen and implemented to increase the power capacity and power supply time of the energy storage devices in the situation of bus failures. Meanwhile
the constant voltage control based on the carrier phase shifting is adopted to reduce the voltage deviations and current ripples
thus improving the power quality. Secondly
to cope with the power fluctuations of distribution networks and to shorten the transient response time
the dynamic response process of the storage converters output current is analyzed in detail
and the small signal model is built. Thirdly
based on the above analysis
a feedforward control strategy is proposed by introducing the voltage deviation into the inner current loop
and the strategy's drawbacks are analyzed and improved. Finally