A number of DC 50 Hz protection malfunctions have occurred in recent years in China Southern power grid due to no-load closing of the converter transformers. The main cause is that the sympathetic inrush current of the operating converter transformer contains abundant positive-sequence second harmonic
which has been transformed to 50 Hz harmonic by converter. This paper analyzes the impact of the DC operation conditions
such as the AC system voltage and DC transmission power
on the tap of converter transformer and AC filters
which changes the positive-sequence second harmonic of sympathetic current finally. It also analyzes the imbalances of positive-sequence second harmonic of the double circuit DC transmission lines from the view of the positions of poles
current interconnection and so on. To avoid the malfunction of 50 Hz protection
some suggestions are proposed
such as decreasing the impedance of AC system
increasing the voltage of AC bus
limiting the transporting power of running pole
etc. The sympathetic inrush current of the other DC transmission line on the same pole as no-load closing pole should be concerned seriously.