Based on the risk of frequency security of the northwest sending-end power grid
a test method for the frequency characteristics of the northwest sending-end power grid is presented. The frequency ramp disturbance is generated by gradually increasing and decreasing the output of the hydropower generating units in the network. Through the analysis of the frequency response of the power grid
the whole frequency static characteristics of the northwest sending-end power grid are measured. At the same time
the actual frequency large-step disturbance is made by the trip of two large-scale hydropower units in the network. The dynamic characteristics of the whole northwest network are measured and the performance of the primary frequency regulation of the conventional power unit is tested. The practical application shows the feasibility of the proposed method.
Adaptive Linear Quadratic Gaussian Primary Frequency Regulation Control Strategy for Doubly-fed Wind Turbines Considering Fatigue Loads
Hierarchical Cluster Cooperative Frequency Control Strategy for Wind Power Bases Considering Differential Frequency Regulation Dead Zones
Simplified Dynamic Model and Primary Frequency Regulation Capability Analysis of Concentrated Solar Power System
Adaptive Control of Primary Frequency Regulation for Electrolytic Aluminum Load Considering Energy Recovery
Related Author
SUN Jian
LIAO Kai
HE Zhengyou
PENG Hexiang
ZHANG Huaiyuan
LIU Jun
QUAN Zhechen
ZHU Shixiang
Related Institution
School of Electrical Engineering, Southwest Jiaotong University
School of Automation and Information Engineering, Xi’an University of Technology
Key Laboratory of Modern Power System Simulation and Control & Renewable Energy Technology, Ministry of Education (Northeast Electric Power University)
College of Electrical Engineering, Sichuan University
Department of Electrical Engineering, Tsinghua University