Flexible interconnection between partitions is a new way to solve the development problems of large urban AC power grid
and the capacity of the interconnection device is the key factor for its cost. The capacity dimensioning method of partitioned flexible interconnection device is presented. Firstly
the basic concept of the device between two partitions of the urban power grid is described. Secondly
through an analysis on power operation range of the device based on the modular multi-level converter(MMC)
the piecewise linear relation between the capacity and the maximum output of reactive power is established
and the methods of improving the output of reactive power are obtained. Thirdly
the capacity dimensioning method of the device is put forward according to the active power demand and the reactive power demand. The active power demand is for solving the overload problems after faults
while the reactive power demand is to solve dynamic voltage instability problems when the transient faults occur. The capacity dimensioning method also considers whether the power support will destroy the security of the sending-end partition or lead to overload of the link lines. Finally
the capacity dimensioning method is applied to the world's first 220 kV partitioned flexible interconnection demonstration project.
Multi-objective Optimization of Regional Reactive Power Reserve in Hybrid System with Wind, Photovoltaic and Energy Storage Considering Fault Scenario Set
基于转供逻辑约束的城市电网运行阻塞控制模型
考虑环境成本的城市电网最优潮流模型
城市电网自愈控制体系结构
Related Author
Sipeng HAO
Yangfei ZHANG
Xiaochun XU
Zemei DAI
Wenlong WU
Guangyu CHEN
TANG Xiaojun
JIN Yong
Related Institution
School of Electric Power Engineering, Nanjing Institute of Technology
NARI Group Corporation (State Grid Electric Power Research Institute)
State Grid Huaian Power Supply Company, Huaian
School of Electrical and Electronic Engineering, North China Electric Power University
School of Electrical Engineering and Information, Sichuan University