To improve the economy and security of the security-constrained optimal power flow(SCOPF)
a corrective security-constrained optimal power flow(CSCOPF)with the control of flexible AC transmission system(FACTS)devices is proposed based on the DC power flow. The FACTS device corrective action is adopted to control the line power flow within the allowable range while a contingency occurs. As the proposed model is a large-scale
non-convex and nonlinear model
it is hard to solve directly. First
the model is transformed into a mixed integer linear program(MILP)model by the Big-M method. Second
the Benders decomposition is used to decouple the proposed model into an optimal power flow master problem and an N-1 contingency check subproblem. Third
the non-convex subproblem is transformed into a linear program by fixing the binary variable
which can return the corresponding Benders cuts to the master problem. The proposed model and solution technique are tested on a 6-bus system and an IEEE RTS-79-bus system. Numerical results show that CSCOPF with the control of FACTS devices will leads to a lower operation cost. This work is supported Post-doctoral Science Foundation of China(No. 2016M590693).
Integrated Optimal Clearing Method of Day-ahead Spot Market for Hybrid AC/DC Power System
Decision-making Method of Corrective Control for Wind Power System with Unified Power Flow Controller Based on Successive Approximated Linear Programming
Related Author
LOU Xiansi
JIANG Xiaoliang
YU Linlin
WEN Yunfeng
DENG Buqing
Mohammad SHAHIDEHPOUR
Yiyun YAO
Dan XU
Related Institution
College of Electrical Engineering, Zhejiang University
Economic Research Institute of State Grid Fujian Electric Power Company
Economic Research Institute of State Grid Henan Electric Power Company
College of Electrical and Information Engineering, Hunan University