In conjunction with Xiamen flexible DC power transmission demonstration project
the scheme and engineering application of flexible DC control and protection system are researched
including the hierarchical structure of control and protection system
the basic control strategy of the pole control system
structure of control system
the interface features between the pole control system and the valve control system and the configuration of the DC protection system function. In order to verify the work correctness between the pole control system
the valve control system and the converter valves
and prevent large current appearing for the first time de-blocking from damaging the converter valves
this paper puts forward the passive inverter test scheme for the true bipolar topological structure system. Field test results have proved the validity of the triggering phase sequence by valve groups
fully compensating for the time delay of the control system. The results of reactive power and active power step test show that the control system meets the performance requirement on rapidity
reliability and flexibility. The results of DC protection trip test show that the logic function is correct
the converter valves are blocked correctly and the breaker trips correctly.
Analysis and Identification of Line Breakage Fault for Flexible DC Transmission System Based on Improved Pole-mode Transformation
Adaptive Distance Protection Method for AC Lines Connected with Flexible DC Transmission System
Related Author
HE Tingyi
ZHAO Wei
SHAO Zongxue
SHU Hongchun
SHU Hongchun
SHAO Zongxue
ZHAO Wei
HE Tingyi
Related Institution
Collaborative Innovation Center for Fault Detection and Protection Control of Smart Grid (Co-built by Province and Ministry)(Kunming University of Science and Technology)
Faculty of Mechanical and Electrical Engineering, Kunming University of Science and Technology
Faculty of Electric Power Engineering, Kunming University of Science and Technology
School of Electrical Engineering, Sichuan University