As the electrical entity boundary installed at both ends of the high voltage direct current(HVDC)transmission line has the ability to block high-frequency components
the start voltage caused by the external fault changes gently and amplitude is small; the start voltage caused by the line fault changes steeply when amplitude is large and the time-domain waveform is shown shaking violently. Principal component analysis(PCA)is used to extract time domain features of pole fault voltage and project the time domain features on to PCA space and form cluster point clusterings of external fault and line fault constituting cPC1 and cPC2 coordinates. Hence the characterization and distinction of external fault and internal line fault. After fault
the Euclidean distance between the projection values of fault data mapped to PCA space and the cluster centers of PCA identification element is used to distinguish internal and external faults adaptively. The large number of measured data tests show that this method has the ability to interfere without lightning disturbance
samples dithering
harmonic interference and other factors
while improving the protection performance of traveling wave protection with du/dt as the core. And if the historical fault data is reusable to increase PCA cluster point clusterings
PCA fault identification element can continue to improve. This work is supported by National Natural Science Foundation of China(No. 51267009)and National Natural Science Foundation of China-Yunnan(No. U1202233).