The conventional passive and active islanding detection methods have large non-detection zones when employed to detect the islanding of the photovoltaic(PV)power station. The changing situation of voltage amplitude and frequency before and after islanding and failure mechanism of the typical conventional active islanding detection method is analyzed firstly. Then the centralized islanding detection method for PV power station is proposed. According to the structural characteristics of centralized reactive power compensation in the PV power station
when the low output active power of PV power station may match the consumed active power of local loads
regulating the power factor to fluctuate within a narrow range by controlling reactive power output by static var generator(SVG)
leading to the mismatching of reactive power between PV power station system and local loads
and islanding is detected accordingly. Theoretical analysis and simulation result has proven that the proposed method can accurately detect islanding of PV power station without none detection zone.
Combined Identification Method for High Proportion of Abnormal Operation Data in Photovoltaic Power Station
Islanding Detection Method for Multiple Distributed Generators Based on Fixed Frequency Control of Inverter
General Solution Method for Non-detection Zone of Droop-controlled Islanding Detection in Microgrid
Related Author
CHEN Yonghua
LI Xue
YANG Di
LIU Xianchao
JIANG Tao
LI Guoqing
YE Lin
CUI Baodan
Related Institution
NARI Group Corporation(State Grid Electric Power Research Institute)
Key Laboratory of Modern Power System Simulation and Control & Renewable Energy Technology, Ministry of Education (Northeast Electric Power University)
College of Information and Electrial Engineering, China Agricultural University
East China Branch of State Grid Corporation of China