the high-power photovoltaic gird-connected inverter should have the zero voltage ride-through(ZVRT)ability of avoiding automatic off-grid phenomenon under the condition of low voltage
which will affect the stable operation of power system. Based on an analysis of the standard about ZVRT of photovoltaic grid-connected inverter
some key technologies including the separation of positive from negative sequence of grid voltage
phase-lock loop(PLL)
the control strategy of active/reactive current
the control strategy of inverter under the condition of unbalanced grid voltage
etc are discussed. In addition
the leading phase compensation for the feed-forward component of grid voltage is proposed and introduced into the current loop of control system to limit the current overshoot during the transients of ZVRT. The effectiveness of the proposed ZVRT control strategy is verified by simulation on RTDS and experimental results of a 500 kW prototype.