First the necessity of bipolar operation with station ground mat in Puer rectifying station of Puqiao ultra high voltage direct current(UHVDC)replacing electrode is analyzed
and then the bipolar operation feasibility is studied in depth
including verification of thermal stability of station ground mat
verification of contact voltage and stepping voltage are checked. Some control and protection optimizations are proposed to avoid big current injecting into station ground mat and ensure the safety of system
people and equipment
including synchronous unlock and lock logic
bipolar current tracking
bipolar synchronous tripping logic
76SG and 87GPS protection in rectifying station and 60EL in inverting station. On-site operation shows that optimizations of direct current(DC)station control
pole control and DC protection can satisfy bipolar operation with station ground mat
and the safety requirements of primary equipment
secondary equipment and people all can meet the proposed standards.