In conventional high voltage direct current (HVDC) power transmission system
frequency controller is configured on the rectifier side. The inverter frequency control can’t be realized when telecommunication is interrupted between stations due to no signals of its inverter to be sent to the rectifier. An inverter-side frequency control method is proposed
which is suit for a DC system startup strategy and an automatic switching strategy between constant current control and constant voltage control when the telecommunication status is instable. In the end
the practicability and reasonability of the proposed strategy are verified by the real time digital system (RTDS) simulation results. The strategy provide a good reference for inverter-side frequency control without telecommunication between stations.
Analysis on Characteristics of DC Dynamical Power and Frequency Response for AC-DC-AC Asynchronous-interconnection System Under Quasi-synchronous Control
Inertia Requirement of Power System: Concepts, Indexes, and Evaluation Method
Dynamic Inertia of Grid-connected Converter with Additional Frequency Control and Its Quantitative Evaluation
Related Author
WANG Kailun
SONG Qiang
ZHAO Biao
LIU Wenhua
YU Zhanqing
ZENG Rong
LI Chongtao
CHEN Yiping
Related Institution
School of Electrical Engineering, Xi’an Jiaotong University
Power Dispatching and Control Center of China Southern Power Grid
Electric Power Research Institute of China Southern Power Grid Company Limited
College of Electrical and Information Engineering, Hunan University