Conductor resistance changes with changing conductor temperatures
which shows that power flow is influenced by environmental factors. In consideration of the relationship between line temperature
line resistance and power flow
this paper presents a power flow formulation for distribution network with the electrothermal coupling effect taken into account. In the formulation
line resistance is a variable rather than a constant as is usual with the traditional power flow method. An extended power flow calculation for distribution system based on the normal backward/forward sweep power flow algorithm is proposed to address the computational complexity of the formulation
in which the line thermal balance equation is embedded in the forward sweep
as well as the line temperature
line resistance and power flow are dynamically updated during the process of iteration. Consequently
the power flow calculation for distribution network considering the electrothermal coupling effect is realized briefly and efficiently. Two case studies using an IEEE 14-bus distribution network and a 118-bus distribution network show that the electrothermal coupling effect has a profound impact on the power flow
while power flow calculation based on constant resistance may lead to significant errors.