Automation of Electric Power SystemsVol. 39, Issue 20, Pages: 141-145(2015)
作者机构:
广东电网有限责任公司电力科学研究院,广东省,广州市,510080
作者简介:
基金信息:
DOI:
CLC:
Published:2015
稿件说明:
移动端阅览
ZHANG Junfeng. [J]. Automation of electric power systems, 2015, 39(20): 141-145.
DOI:
ZHANG Junfeng. [J]. Automation of electric power systems, 2015, 39(20): 141-145.DOI:
励磁系统调差系数优化整定存在的风险分析
摘要
目前广东电网“八交八直”的受电通道中
负荷超80 GW的特大型受端电网的电压稳定问题突出
电网动态无功支撑不足成了电网电压稳定问题中亟待解决的问题。发电机作为电网的重要无功电源
有丰富的无功储备可以挖掘
且不用增加投资。为更大限度地调用发电机的无功资源
发挥负调差在提高机组无功出力中的作用
文中就采用负调差对机组的安全稳定运行带来的潜在风险进行了全面梳理和研究
重点研究了调差对机组间无功分配、机组阻尼
以及对电力系统稳定器(PSS)和自动电压控制(AVC)的影响。结合广东电网的实际情况
给出了调差系数从0变化到-10%对机组及电网的稳定影响风险可控的结论
为发电机组的调差优化整定工作提供了借鉴。
Abstract
Guangdong power grid is a receivingend power grid at the end of eight AC main lines and eight DC main lines
in which the power load exceeds 80 GW. The problem of voltage stability is thus outstanding and the insufficient dynamic reactive power support for power grid is an issue demanding prompt solution for the voltage stability. As an important reactive power supply
generators have abundant reactive power reserves to be used
while there’s no need to increase investment. To make bigger use of the generator reactive power resource and bring into play the role of negative reactive current compensation in improving the reactive power output of the unit
the paper adopts negative reactive current compensation of security and potential risk for the stable operation of unit
focusing on the reactive current compensation to the influence of reactive power allocation between the units
the influence on unit damping adjustment
and the effects on power system stabilizer (PSS) and automatic voltage control (AVC). By referring to the actual situation in Guangdong power grid
it is concluded that unit and grid stability risks are controllable if the negative reactive current compensation varies from 0 to -10%. It is a meaningful reference for the optimization and setting of the generator reactive current compensation coefficient.