A coordinated control method for distribution static synchronous compensator (DSTATCOM) group based on slope adjustment is proposed to solve the coordinated control problem of reactive voltage with multi-distributed generators (DGs) in the same area. By taking into account the parameters of grid
the relationship between the reactive voltage
the output active current of DG and the output reactive current of DSTATCOM is established
Then
based on the maximum capacity of DSTATCOM
the slope adjustment of each DSTATCOM is set up to rationally allocate the reactive power output of each device. Thirdly
the reactive current proportional gain which is constituted by the sum of the slope setting and reactance of the corresponding line to the reference voltage is taken as a negative feedback to constitute the new voltage reference value of the DSTATCOM
and the coordinated control strategy of DSTATCOM group is established based on the slope adjustment. Finally
a network with dual DGs and DSTATCOMs is simulated to show that the slope setting will coordinate the dynamic reactive behavior of each DSTATCOM
allocate the output reactive power proportionally and stabilize the system voltage without real-time communication between the controllers.
Construction Scheme of Voltage-supporting Renewable Energy Station Based on Distributed Synchronous Condensers—Part Two Coordinated Control Strategy and Test Verification
Control Strategy and Capacity Selection of DRU-MMC Hybrid Converters for Offshore Wind Power
Multi-timescale Frequency Regulation Control of Flexible Resources in Virtual Power Plant
Related Author
LIANG Hao
QIN Chuan
XIE Huan
LIANG Beihua
WU Tao
WANG Xuanyuan
WU Long
GAN Huichen
Related Institution
State Grid Jibei Electric Power Research Institute
Power Dispatch and Control Center of State Grid Jibei Electric Power Co., Ltd.
NR Electric Co., Ltd.
School of Electric Power, South China University of Technology
Guangdong Key Laboratory of Clean Energy Technology (South China University of Technology)