The large-capacity static var compensator (SVC) is applied in actual projects. Theoretical analysis and simulation results show that
a large amount of 3
5 and other odd harmonic currents will be injected into the fault-point from the SVC equipment when faults occur on the low-voltage side of the transformer. What is more
the harmonic current is significant in content and slow in attenuation rate. Traditional transformer differential protection usually adopts harmonic blocking methods to prevent incorrect operation from current transformer saturation at external faults
magnetizing inrush current and over-excitation. Harmonic currents produced by the large-capacity SVC equipment may make the harmonic blocking element make a wrong judgment
leading to slow operation of the differential protection or even failure to operate. To solve this problem
the 2nd harmonic rather than 3rd harmonic should be used in TA saturation criterion. Digital simulation test is performed to verify the validity of theoretical analysis.
Characteristic Analysis of Second Harmonic of Magnetizing Inrush Current with No-load Transformer Energization
Countermeasures for Mal-operation of Zero-sequence Differential Protection of Converter Transformer Under Inrush Current Condition
Transformer Differential Protection Criterion Based on Reconstructed Trajectory of Current Characteristics in Two-dimensional Space
Related Author
YANG Qing
ZHENG Tao
XIAO Shiwu
HUANG Shaofeng
LIU Wanshun
HUANG Jingwen
DU Zhiye
XU Jian
Related Institution
The Key Laboratory of Power System Protection and Dynamic Security Monitoring and Control Under Ministry of Education, North China Electric Power University
Central China Branch of State Grid Corporation of China