researches on the adaptive reclosure lack an analytic expression for beat frequency current about whether the beat frequency current definitely exists and the range of amplitude of the current in adaptive reclosure. The amplitude may be nonexistent or too small when the single-phase transient fault disappears
which will affect the reliability of reclosing determination. The beat frequency current in the shunt reactor is not only affected by sound phase voltage but also by the initial state of components of transmission line when fault disappears. Based on the superposition principle
the complete expression of beat frequency current is obtained
by an analysis of which the minimum beat frequency current and conditions for its occurrence are obtained. It is concluded that the beat frequency current being zero belongs to small probability event. The current is affected by fault time
arc duration
arc resistance
phase angle difference and fault location that make the amplitude obvious. If the amplitude is too small
it will affect the reliability of the reclosing determination. The paper gives the range of amplitude of the beat frequency current on 500 kV transmission lines using the method of the orthogonal experiment in mathematical statistics
proving the beat frequency current can be applied to engineering. This work is supported by National Natural Science Foundation of China(No. 50877062).
Three-phase Adaptive Reclosure Scheme Based on Characteristic Voltage Injection for Transmission Line Equipped with Unified Power Flow Controller
超高压有并联电抗器线路无故障重合闸研究
Evaluation of Compound-disaster Failure Rate for Transmission Lines from Perspective of Whole Reductionism Thinking —Part Two Algorithm and Application
Evaluation of Compound-disaster Failure Rate for Transmission Lines from Perspective of Whole Reductionism Thinking —Part One Framework Design
Related Author
Tao ZHENG
Yunpeng WANG
Jiaxuan MA
Huanhuan QI
LU Yan
ZHENG Yuping
SHEN Jun
WU Tonghua
Related Institution
State Key Laboratory of Alternate Electrical Power System with Renewable Energy Sources (North China Electric Power University)
State Key Laboratory of Advanced Power Transmission Technology (Global Energy Interconnection Research Institute Co., Ltd.)