between the generator terminal and the step-up transformer
generator circuit breakers are installed
and generator circuit breaker failure protection is also installed. This paper analyzes the protections and the value settings of the nuclear power plant generator
and points out the problems in the generator circuit breaker failure protection design. First
in the protection of some jump starter generator circuit breakers
de-excitation
and the main valve closing
as the current criteria are not satisfied
the starter generator circuit breaker failure protection cannot be directly activated. Secondly
during the turbo-generator program tripping process
the generator circuit breakers break down and cannot trip
neither can the generator circuit breaker failure protection be activated. Based on the harm caused by these problems
this paper proposes some improvements on the nuclear power plant generator breaker failure protection design
further improving the generator circuit breaker failure protection design in the nuclear power plant.