In the process of solving the power system time-delay stability via the linear matrix inequality (LMI) criterion
the high dimensions in the dynamic model of power systems may result in the over abundance of unknown variables and unacceptable length of calculation time. In order to surmount this difficulty
this paper initially converts the power system linear model with single time-delay to a state-space model with the input and output component. Furthermore
the extended model is simplified via the well-developed state-space based model reduction method. As a consequence
the quantity of unknown variables will substantially decrease while the system’s crucial dynamic features are reserved. Finally
on the basis of the simplified model
the LMI technique and the parameter transform tool
a new time-delay stability criterion with better performance
is obtained. The proposed method is used in the WSCC 3-machine 9-bus and IEEE 10-machine 39-bus system with single time-delay component
and a comparison of stability margin solving results between the two systems is made with the binary search method. The numerical results indicate that the simplified model of time-delay system generates fewer errors in the calculation of stability margin than those of the model without simplification
Time-Frequency Domain Dissipation Energy Flow Method for Forced Oscillation Source Location in Power System
Related Author
XIE Hai
ZHAO Linsheng
JIN Rongyu
YANG Dong
YAO Jun
ZHANG Tian
JIANG Tao
YE Nan
Related Institution
State Key Laboratory of Power Transmission Equipment Technology (Chongqing University)
Key Laboratory of Modern Power System Simulation and Control & Renewable Energy Technology, Ministry of Education (Northeast Electric Power University)
College of Electrical Engineering, Zhejiang University
National Electric Power Dispatching and Control Center of State Grid Corporation of China
State Key Laboratory of Power Grid Safety and Energy Conservation(China Electric Power Research Institute)